Study of Earthquake Simulation Shaking Table Test on the Capacitor Bank in Untra High-Voltage Substation


Abstract eng:
As routine equipment in UHV substation, capacitor bank gets highly earthquake vulnerability because of its high center of gravity, big quality and low-intensity support structure. It might bring great economic loss if capacitor bank damaged in an earthquake. In this analysis, a model of 110 kV capacitor bank in UHV substation was tested by shaking table first time in China. The dynamic characteristics and seismic response regularities of the model were obtained by testing the acceleration, displacement and strain of the key parts during seismic action. The seismic behavior of 110 kV capacitor bank was verified by the test, and the seismic vulnerable site of the equipment was definite. Also the improvement measures to decrease the seismic response of capacitor bank was proposed.