000021969 520__ $$2eng$$aThe paper summarizes the results of an extensive study conducted at the University of California, Berkeley. A test article representative of a piece of high-voltage substation equipment was studied on a shaking table. It consisted of a support structure and an insulator installed on its top. The support structure was constructed from a HSS with well-separated natural frequencies in both horizontal directions. A porcelain insulator typically used on a 230-kV system was used in the study. A set of four wire ropes was used as a seismic isolation for the system. Two installation cases were considered in the study: (1) fixed base and (2) isolated by wire ropes. As required by the latest draft of IEEE693, a number of component tests was conducted to evaluate the performance of the wire ropes. Based on the results of component testing, detailed numerical models of the seismically protected equipment were generated. Each equipment configuration was subjected to seven time histories matched to the same IEEE693 spectrum. Four of them were modified from historical records and matched to the IEEE693 spectrum in the time domain. The other three excitations were synthetic strong motions matched to the same spectrum. The main objective was to evaluate the variability of the seismic response of the equipment subjected to seven time histories matched to the same response spectrum.

000021969 540__ $$aText je chráněný podle autorského zákona č. 121/2000 Sb.
000021969 653__ $$aSeismic Qualification Testing per IEEE693, Nonlinear System, Finite Element Modeling and Analysis, Shaking Table Tests, Seismic Base Isolation.

000021969 7112_ $$aCOMPDYN 2017 - 6th International Thematic Conference$$cRhodes Island (GR)$$d2017-06-15 / 2017-06-17$$gCOMPDYN2017
000021969 720__ $$aTakhirov, Shakhzod M.$$iLow, Brian$$iRiley, Michael$$iKempner, Leon$$iFujisaki, Eric
000021969 8560_ $$ffischerc@itam.cas.cz
000021969 8564_ $$s9030020$$uhttps://invenio.itam.cas.cz/record/21969/files/18509.pdf$$yOriginal version of the author's contribution as presented on CD, section: [MS20] Seismic resilience of critical infrastructure and lifelines
.
000021969 962__ $$r21500
000021969 980__ $$aPAPER